Comprehensive transient analysis on control system in a photovoltaic power plant under lightning strike

Thumbnail

Göster/Aç

Tam Metin / Full Text (5.677Mb)

Tarih

2022

Yazar

Demirel, Emre
Karaca Dolgun, Gülşah
Keçebaş, Ali

Üst veri

Tüm öğe kaydını göster

Özet

Solar power plants are installed in high and open places to receive high solar radiation. However, this leaves them vulnerable to lightning strike. Lightning strike affects power plants in two ways, directly and indirectly. Direct lightning strikes can be prevented by using lightning protection systems. However, under the indirect effect of a lightning strike, the surrounding electronic devices may be damaged due to the induced voltage. In a solar power plant with a lightning protection system in Turkey, it was stated that the bypass diodes failed after a lightning strike. In this study, it is aimed to examine the effects of indirect lightning strike on the PV module. For this reason, different lightning pulse amplitudes were injected into the system and the effects of three parameters on the induced voltage were investigated with an EMT type program. These parameters were the cable lengths, cable cross-sections and the number of PV arrays. Four different panel configurations were performed in the EMT type program. Data was taken from the solar power plant in Turkey was used in fourth configuration. It was concluded that when the lightning strike fell on the air termination bar, bypass diodes in the nearest PV array were affected, and this effect decreased as the array distance increased. However, as the amplitude of the lightning strike increased, arrays in the far-distance were also affected. It has been seen that the results obtained were compatible with the malfunction information received from the solar power plant

Kaynak

Solar Energy

Cilt

233

Bağlantı

https://doi.org/10.1016/j.solener.2022.01.037
https://hdl.handle.net/20.500.12809/9789

Koleksiyonlar

  • Enerji Sistemleri Mühendisliği Bölümü Koleksiyonu [104]
  • Scopus İndeksli Yayınlar Koleksiyonu [6219]
  • WoS İndeksli Yayınlar Koleksiyonu [6466]



DSpace software copyright © 2002-2015  DuraSpace
İletişim | Geri Bildirim
Theme by 
@mire NV
 

 




| Politika | Rehber | İletişim |

DSpace@Muğla

by OpenAIRE
Gelişmiş Arama

sherpa/romeo

Göz at

Tüm DSpaceBölümler & KoleksiyonlarTarihe GöreYazara GöreBaşlığa GöreKonuya GöreTüre GöreDile GöreBölüme GöreKategoriye GöreYayıncıya GöreErişim ŞekliKurum Yazarına GöreBu KoleksiyonTarihe GöreYazara GöreBaşlığa GöreKonuya GöreTüre GöreDile GöreBölüme GöreKategoriye GöreYayıncıya GöreErişim ŞekliKurum Yazarına Göre

Hesabım

GirişKayıt

DSpace software copyright © 2002-2015  DuraSpace
İletişim | Geri Bildirim
Theme by 
@mire NV
 

 


|| Politika || Rehber|| Yönerge || Kütüphane || Muğla Sıtkı Koçman Üniversitesi || OAI-PMH ||

Muğla Sıtkı Koçman Üniversitesi, Muğla, Türkiye
İçerikte herhangi bir hata görürseniz, lütfen bildiriniz:

Creative Commons License
Muğla Sıtkı Koçman Üniversitesi Institutional Repository is licensed under a Creative Commons Attribution-NonCommercial-NoDerivs 4.0 Unported License..

DSpace@Muğla:


DSpace 6.2

tarafından İdeal DSpace hizmetleri çerçevesinde özelleştirilerek kurulmuştur.