Basit öğe kaydını göster

dc.contributor.authorAlkan, Mehmet Ali
dc.contributor.authorKecebas, Ali
dc.contributor.authorYamankaradeniz, Nurettin
dc.date.accessioned2020-11-20T16:19:18Z
dc.date.available2020-11-20T16:19:18Z
dc.date.issued2013
dc.identifier.issn0360-5442
dc.identifier.issn1873-6785
dc.identifier.urihttps://doi.org/10.1016/j.energy.2013.08.017
dc.identifier.urihttps://hdl.handle.net/20.500.12809/3729
dc.descriptionWOS: 000326773400044en_US
dc.description.abstractThis study presents the exergoeconomic analysis and evaluation in order to provide cost based information and suggests possible locations/components in a GDHS (geothermal district heating system) for improving the cost effectiveness. The analysis is based on the SPECO (specific exergy costing) method, and used to calculate exergy-related parameters and display cost flows for all streams and components. As a real case study, the Afyon GDHS in Turkey is considered based on actual operational data. The obtained results show that the unit exergy cost of heat produced by the Afyon GDHS is calculated as average 5624 $/h. The HEX (heat exchanger)-III among all components should be improved quickly due to the high total operating cost rate and relative cost difference. The HEX-I and PM (pump)-V have the highest exergoeconomic factors among all other system components due to the high owning and operating costs of these components. The heat production costs per exergy unit for all the HEXs decrease due to the high exergy destruction cost rate of the system, while the well head temperature and ambient temperature increase. The SPECO method may be used to improve the cost effectiveness according to exergy rates in GDHSs as a thermal system. Crown Copyright (C) 2013 Published by Elsevier Ltd. All rights reserved.en_US
dc.description.sponsorshipAfyon Geothermal Inc., Turkeyen_US
dc.description.sponsorshipThe authors would like to thank for the support provided by the Afyon Geothermal Inc., Turkey.en_US
dc.item-language.isoengen_US
dc.publisherPergamon-Elsevier Science Ltden_US
dc.item-rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectGeothermal Energyen_US
dc.subjectDistrict Heating Systemen_US
dc.subjectThe SPECO Methoden_US
dc.subjectExergoeconomic Evaluationen_US
dc.titleExergoeconomic analysis of a district heating system for geothermal energy using specific exergy cost methoden_US
dc.item-typearticleen_US
dc.contributor.departmenten_US
dc.contributor.departmentTemp[Alkan, Mehmet Ali] Mugla Sitki Kocman Univ, Dept Elect & Energy, Ula Ali Kocman Vocat High Sch, TR-48640 Mugla, Turkey -- [Kecebas, Ali] Mugla Sitki Kocman Univ, Fac Technol, Dept Energy Syst Engn, TR-48000 Mugla, Turkey -- [Yamankaradeniz, Nurettin] Uludag Univ, Vocat Sch Tech Sci, Dept Air Conditioning & Cooling Technol, TR-16059 Bursa, Turkeyen_US
dc.identifier.doi10.1016/j.energy.2013.08.017
dc.identifier.volume60en_US
dc.identifier.startpage426en_US
dc.identifier.endpage434en_US
dc.relation.journalEnergyen_US